Level Sensor Calibration For Square And Stepped Tanks For Rapidlogger Systems

Level Sensor Calibration For Square And Stepped Tanks For Rapidlogger Systems

This tech note describes the following processes:

  • Set up software
  • Adjusting sensor to eliminate lag time and readings becoming frozen
  • Set up for linearization for a Stepped tank style

Equipment and Software needed:

  • VegaFlex 81 series sensor
  • Power source of 6vDC (MAX)
  • Vega Connect 4 with connection box
  • VEGA-DTM 1.73.1 -http://www.vega.com/downloads/Software/DTM-Collection.exe
  • License – guided microwave -3C73-E3F1-1480-1232-F665

Set up Software

  1. Download Vega DTM 1.73.1 from link
    1. This will install the PACTWare 4.1 software as well
  2. Take off Vega LCD interface and replace with Vega connect interface seen in figure 1. If Vega connect interface is not available you can use any Hart Modem as well.

Vega Connect Oilfield Interface

Figure 1

  1. Install USB from sensor to PC and connect power source to sensor
  2. Run PACTWare 4.1
  3. Click Start. This will connect the sensor
  4. It will give 3 options. Click “extended adjustment”
  5. Click drop box for help and click “info about” seen in figure 2. At the bottom where it says license is where you will put in the license given above

TDR Sensor for Well Monitoring Software

Figure 2

  1. Click accept and software set up is complete

Adjust Sensor

  1. Reconnect LCD Vega interface.
  2. Press OK
  3. Press Extended Adjustment
  4. Press setup
  5. Press Application
  6. Press Application
  7. OK and switch to demonstration mode
  8. ESC to front screen.
  9. To change damping we will follow same steps from 10-12
  10. Press Damping. Here you can adjust the time
  11. To change averaging we will start from step 11
  12. Press additional adjustments
  13. Press special parameter
  14. Input SW
  15. Press SP 05. Here you can change the averaging time
  16. The sensor is now ready for a square tank style

Stepped Tank Style

For a Stepped Tank style we will have to change the geometry of the tank in the PACTware 4.1 Software.

  1. Follow steps 2-6
  2. Under setup click on Type of linearization seen in figure 3

Stepped Tank Style Monitoring Software

Figure 3

  1. Across from linearization type is a drop box. Change this to User Programmable if not in this already.
  2. Under that click on Open the linearization assistant
  3. Change your selection of the linearization to Calculation assistant. Click Next
  4. Change Vessel type to Defragmented tank. Click Next
  5. Under segments click on the symbol or name of pyramid.
  6. Click the delete segment button (X). See figure 4

Stepped Tank Style Linearization Monitoring

Figure 4

  1. Now for the 2 Cuboids you can type in your dimensions per schematic.
  2. Change Scaling unit to bbl. Click Next till you get to finish
  3. Click finish
  4. It will update and save to sensor now.
  5. Click the save button located at the top left of screen. This will save the setup in case you would like to place same setup on another sensor.